Online UPS Memo plus 1KVA-3KVA
MODEL | MP S 1K | MP S 2K | MP S 3K | ||
CAPACITY | VA/W | 1000VA/900W | 2000VA/1800W | 3000VA/2700W | |
INPUT | Voltage Range | 200-290VAC at full load | |||
Frequency Range | 45-55Hz at 50Hz/55-65Hz at 60Hz(auto-detect) | ||||
Phase | Single phase with ground | ||||
Current THDI | <7%(100% nonlinear load) | <7%(100% nonlinear load) | <7%(100% nonlinear load) | ||
Power Factor | >=0.98 | ||||
Generator Input | Support | ||||
breaker | 7A | 16A | 25A | ||
Input Socket | IEC320 C13-10A | IEC320 C20-16A | IEC320 C20-16A | ||
AC power cord | IEC320 C14-10A | IEC320 C19-16A | IEC320 C19-16A | ||
OUTPUT | Voltage | 200/208/220/230/240VAC | |||
Power Factor | 0.9 | ||||
Voltage Regulation | ±2% | ||||
Frequency (Line Mode) | 46-54Hz at 50Hz/56-64Hz at60Hz | ||||
Frequency(Battery Mode) | 50/60Hz±0.02Hz | ||||
Current Crest Ratio | 3:1 | ||||
Harmonic Distortion | <=3% THD(Linear Load) | ||||
<=5% THD(Non-Linear Load) | |||||
Output Waveform | Pure Sinewave | ||||
Outlet | (IEC C13-10A)*3 | (IEC C13-10A)*8 | (IEC C13-10A)*8 (IEC C19-16A)*1 | ||
Overload Capacity | Line Mode | 30S at 100%-150% ;300ms at >150% | |||
Battery Mode | 30S at 100%-150% ;300ms at >150% | ||||
EFFICIENCY | AC Mode | Full load>=89% | Full load>=89% | Full load>=89% | |
Battery Mode | Full load>=84% | ||||
ECO Mode | Full load>=94% | ||||
BATTERY | Number of Batteries Per Set | 3 | 6 | 6 | |
Battery Type | 12V/7Ah/9Ah | 12V/7Ah/9Ah | 12V/9Ah | ||
Backup Time | Estimated remaining time displayed on the LCD | ||||
Recharge Time(to 90%) | 5 Hours | 5 Hours | 5 Hours | ||
Charging Current(Max) | 1.0A | 1.0A | 1.0A | ||
Rated Battery Voltage | 36Vdc | 72Vdc | 72Vdc | ||
charge mode | 3-stage charging | ||||
Protect | Over-voltage /Over-current /Low-voltage | ||||
Battery Socket | Anderson like PowerPole Modular Connectors | ||||
TRANSFER TIME | Mains ←→Battery | 0ms | |||
Mains ←→ Bypass | <4ms | ||||
OPTIONAL FEATURES | Economic Mode(ECO Mode) | Support | |||
INDICATOR | LCD Version(with LED) | Load/Battery/Input/Output/Operating Mode Information | |||
AUDIBLE ALARM | Battery Mode | Sounding every 4 seconds | |||
Low Battery | Sounding every second | ||||
Overload | Sounding twice every second | ||||
Fault | Continuously Sounding | ||||
PHYSICAL | Dimension(W*D*H)mm | 144*409*215 | 199*466*337 | ||
Net Weight(kg) | 13 | 24.6 | 25.5 | ||
ENVIRONMENT | Safety | CB | |||
Operating Environment | 0-40ºC | ||||
Relative Humidity | 0-90%(non-condensing) | ||||
Altitude | <1500m. when >1500m, derating | ||||
Noise Level | <55dB at 1Meter | ||||
INTERFACE | Smart RS-232/USB(Preferential) | Software supports Windows Family,Linus,FreeBSD | |||
Intelligent Slot | SNMP(independent to RS232) | ||||
* If rated input voltage select to be 200V , the low limit is 180V. If rated input voltage select to be 208V , the low limit is 190V. Under other condition the low limit is 200V. |
MEMOPOWER PLUS SERIES
1-3KVA 1:1 PHASE (PF0.9)
FEATURE:
Output power factor up to 0.9.
Three segment charging mode to increase battery service life, optimize recharge time.
Selectable High Efficiency mode of operation.
Cold start function to startup the UPS without utility.
Standard communication options: one RS-232 communication port, one USB communication port, and relay output contacts or SNMP card.
Power Shedding function may turn off uncritical load in battery backup to make longer backup time for critical load.
Extended runtime with up to four Extended Battery Modules (EBPs) per UPS.
Emergency shutdown control through the Remote Emergency Power-off (EPO) port.
Versatile LCD display with setting function.